The analog input isolated safety barrier provides isolated power supply for two-and three wire transmitters in hazardous areas. The 4~20mA signal generated by the transmitter or current source is transmitted from the hazardous area to the safe area output, thereby driving the load in the safe area. For two-or three wire transmitters or current source signals, this safety barrier supports bidirectional communication of the Hart digital signal superimposed on the 4~20mA signal and has a wire breakage alarm function. This product requires independent power supply, with isolated power supply, input, and output terminals.
■ The isolated barrier transmits 4-20mA signals generated by transmitters in hazardous areas, or DC 4-20mA signals, to the safe area.
■ The barrier provides power distribution to the field transmitter. It supports HART digital signals and features line-fault (breakage) alarm functionality.
■ An external power supply of 20-35V DC is required.
■ Supports power supply via DIN-rail bus connectors
Product Dimension

Wiring Diagram

Technical Parameters:
| Item | Parameters |
| Input Signal | Two or three-wire transmitteror current source(HART digital signal) |
| Transmitter distribution voltage | The open circuit voltage is ≤28V, and the output voltage is ≥15.5V when the circuit is 20mA |
| Output in Safety Area |
| Output Signal | Active 4-20mA(HART digital signal) Passive 4~20mA(HART digital signal) optional |
| Output Load | When outputting 20mA, 0-500Ω(customizable) Optional voltage output type, load resistance RL≥ 330kΩ |
| Basic Parameters |
| Supply voltage | 18-35V DC |
| Power consumption | ≤65mA(When 24V power supply, 20mA output) |
| LED indicator | Green-Power indicator |
| Output accuracy | 0.1%F.S (Typical value:0.05% F.S) |
| Response time | 2ms to reach 90% of the final value |
| Temperature drift | 0.005%F.S/℃ |
| Temperature parameters | Working temperature:-20℃~+60℃ Storage temperature:-40℃~+80'C |
| Relative humidity | 10%-95% RH no condensation |
| Insulation strength | Between intrinsically safe side and non-intrinsically safe side (≥3000V AC/min) between power supply and non-intrinsically safe side (≥1500V AC/min) |
| Insulation resistance | ≥100MΩ (Between input/output/power supply) |
| EMC | According to lEC 61326-1(GB/T 18268), IEC 61326-3-1 |
| Wire requirements | Cross-seclion ≥0.5mm2 Insulation strength ≥500V |
| Applicable field equipments | Two, three-wire (HART) transmitter or current source (HART) signal |
| Installation place | Installed in a safe zone, it can be connected tointrinsic safety instruments in hazardous areas up to Zone 0, llC, Zone 20, and lllC |
| Safety Certification |
| Explosion-proof mark | [Exia Ga] IIC, [Exia Da]lllC |
| Explosion-proof standard | GB/T 3836.1-2021 GB/T 3836.4-2021 |
| Terminals 3-2, 3-4 | Um:250VAC/DC Uo=28VDC Io=93mA Po=0.65W Co=0.083uF Lo=4.2mH |
| Terminals 1-2 | Um:250VAC/DC Uo=7.2VDC Io=-- Po=-- Co=12uF Lo=-- |