Analogue Input Isolated Safety Barrier

The analog input isolated safety barrier provides isolated power supply for two-and three wire transmitters in hazardous areas. The 4~20mA signal generated by the transmitter or current source is transmitted from the hazardous area to the safe area output, thereby driving the load in the safe area. For two-or three wire transmitters or current source signals, this safety barrier supports bidirectional communication of the Hart digital signal superimposed on the 4~20mA signal and has a wire breakage alarm function. This product requires independent power supply, with isolated power supply, input, and output terminals.

■ The isolated barrier transmits 4-20mA signals generated by transmitters in hazardous areas, or DC 4-20mA signals, to the safe area.

■ The barrier provides power distribution to the field transmitter. It supports HART digital signals and features line-fault (breakage) alarm functionality.

■ An external power supply of 20-35V DC is required.

■ Supports power supply via DIN-rail bus connectors


Product Dimension


Analogue Input Isolated Safety Barrier


Wiring Diagram

Active Output PHD-11CD-21

Technical Parameters:

ItemParameters
Input SignalTwo or three-wire transmitteror current source(HART digital signal)
Transmitter distribution voltageThe open circuit voltage is ≤28V, and the output voltage is ≥15.5V when the circuit is 20mA
Output in Safety Area
Output SignalActive 4-20mA(HART digital signal)
Passive 4~20mA(HART digital signal) optional
Output LoadWhen outputting 20mA, 0-500Ω(customizable)
Optional voltage output type, load resistance RL≥ 330kΩ
Basic Parameters
Supply voltage18-35V DC
Power consumption≤65mA(When 24V power supply, 20mA output)
LED indicatorGreen-Power indicator
Output accuracy0.1%F.S (Typical   value:0.05% F.S)
Response time2ms to reach 90% of the   final value
Temperature drift0.005%F.S/℃
Temperature parametersWorking   temperature:-20℃~+60℃
Storage temperature:-40℃~+80'C
Relative humidity10%-95% RH no condensation
Insulation strengthBetween intrinsically safe side and non-intrinsically safe side (≥3000V AC/min) between power supply and non-intrinsically safe side (≥1500V AC/min)
Insulation   resistance≥100MΩ (Between   input/output/power supply)
EMCAccording to lEC   61326-1(GB/T 18268), IEC 61326-3-1
Wire requirementsCross-seclion   ≥0.5mm2
Insulation strength ≥500V
Applicable field   equipmentsTwo, three-wire (HART) transmitter or current source (HART) signal
Installation placeInstalled   in a safe zone, it can be connected tointrinsic safety instruments in   hazardous areas up to Zone 0, llC, Zone 20, and lllC
Safety Certification
Explosion-proof   mark[Exia Ga] IIC, [Exia   Da]lllC
Explosion-proof   standardGB/T 3836.1-2021
GB/T 3836.4-2021
Terminals 3-2, 3-4Um:250VAC/DC  Uo=28VDC    Io=93mA  Po=0.65W  Co=0.083uF    Lo=4.2mH
Terminals 1-2Um:250VAC/DC  Uo=7.2VDC    Io=--  Po=--  Co=12uF    Lo=--